Schneider Electric MasterPact NW63H1 6300A 4-Pole Fixed ACB – 100kA, Without Trip Unit

59.538.74 AED
In Stock

The Schneider Electric MasterPact NW63H1 48121 is a 6300A, 4-pole fixed air circuit breaker (ACB) basic frame designed for high-capacity low-voltage power distribution. It features 100kA ultimate and service breaking capacity at 440V AC, a 690V AC rated operational voltage, and is supplied without a Micrologic trip/control unit.

In Stock
Add to wishlist1 person favorited this product

Description

The Schneider Electric MasterPact NW63H1 is the highest-current 6300A frame in the MasterPact NW range, intended for large industrial and infrastructure LV switchboards where very high current-carrying and short-circuit capabilities are required. Reference 48121 is the 4-pole fixed-mount basic frame and is supplied without a protection/control unit.

With an H1 breaking-capacity class, the MasterPact NW63H1 48121 provides 100kA Icu and Ics at 440V AC. The breaker has a 6300A rated current, 1000V insulation voltage, and 12kV impulse withstand voltage, making it suitable for demanding high-current LV distribution applications.

The 4-pole configuration allows switching of the three phases and neutral. This makes it suitable for applications where neutral switching/isolation is required, subject to the electrical system design and applicable standards. The fixed construction is intended for permanent installation in the switchboard and should not be presented as a field-convertible drawout unit.

Reference 48121 is a basic frame without a trip unit. A compatible Micrologic control unit must be selected separately according to the required overload, short-circuit, earth-fault, metering and communication functions.

Specification Details
Manufacturer Schneider Electric
Product Range MasterPact NW
Circuit Breaker Name MasterPact NW63H1
Reference / Catalogue Number 48121
Replacement Reference LV948121
Product Type Air Circuit Breaker (ACB) Basic Frame
Application Low-Voltage Power Distribution
Rated Current (In) 6300A
Number of Poles 4P / 4 Pole
Mounting Mode Fixed
Control / Trip Unit Without Trip / Control Unit
Performance Level H1
Rated Operational Voltage (Ue) 690V AC, 50/60Hz
Rated Insulation Voltage (Ui) 1000V AC, 50/60Hz
Rated Impulse Withstand Voltage (Uimp) 12kV
Rated Ultimate Breaking Capacity (Icu) 100kA at 440V AC
Rated Service Breaking Capacity (Ics) 100kA at 440V AC
Rated Short-Time Withstand Current (Icw) 100kA for 1s; 100kA for 3s
Rated Short-Circuit Making Capacity (Icm) 220kA at 525V AC
Utilization / Selectivity Category Category B
Suitability for Isolation Yes, conforming to IEC 60947-2
Network Type AC
Rated Frequency 50/60Hz
Control Type Push-button / manually operated
Circuit Breaker CT Rating 6300A
Protection Type Without Protection / Trip Unit
Maximum Breaking Time 25ms
Closing Response Time <80ms
Connection Pitch 230mm
Mechanical Durability 5,000 cycles without maintenance / 10,000 cycles with maintenance
Electrical Durability AC-3: 6,000 cycles at 440/690V AC without maintenance
Ambient Operating Temperature -25°C to +70°C
Neutral Position Left
Main Connection Bolted connection
Standard IEC 60947-2
Certification ASTA
Mercury Free Yes
RoHS Applicable / exemption information available
Weight Approx. 145.13kg

Key Features

  • 6300A rated current
  • 4-pole / 4P configuration
  • MasterPact NW63H1 air circuit breaker frame
  • Fixed-mount construction
  • 100kA H1 breaking capacity
  • 100kA Icu and Ics at 440V AC
  • 690V AC rated operational voltage
  • 1000V rated insulation voltage
  • 12kV impulse withstand voltage
  • 100kA short-time withstand current
  • 220kA short-circuit making capacity at 525V AC
  • Category B selectivity
  • Suitable for isolation according to IEC 60947-2
  • Without Micrologic trip/control unit
  • Manual push-button operation
  • Designed for high-capacity LV power distribution
  • 4-pole neutral switching capability
  • Suitable for main incomer and bus-tie applications

Applications

The Schneider Electric MasterPact NW63H1 6300A 4P ACB is suitable for:

  • Main incomer protection
  • High-capacity LV switchboards
  • Bus coupler / bus-tie applications
  • Industrial power distribution
  • Large commercial electrical installations
  • Infrastructure power systems
  • Data-centre power distribution
  • Generator and mains changeover systems where 4-pole switching is required
  • High-current feeder protection
  • Large manufacturing facilities
  • Utility and infrastructure switchboards
  • 6300A low-voltage power distribution systems

For applications requiring specific protection functions, the appropriate Micrologic control unit and accessories must be selected separately.

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.