Schneider Electric MasterPact NW40H1 4000A 4-Pole Fixed ACB – 65kA, Without Trip Unit

28.344.60 AED
In Stock

The Schneider Electric MasterPact NW40H1 48097 is a 4000A, 4-pole fixed air circuit breaker (ACB) frame designed for high-capacity low-voltage power distribution. It features an H1 performance level with 65kA Icu at 440V AC, 690V AC rated operational voltage, and is supplied without a control/trip unit.

In Stock
Add to wishlist1 person favorited this product

Description

The Schneider Electric MasterPact NW40H1 48097 is a high-current air circuit breaker frame from the MasterPact NW range, designed for demanding LV electrical distribution systems. With a 4000A rated current, 4-pole configuration and fixed mounting, it is suitable for high-capacity main incomers, bus couplers and heavy sub-distribution applications.

The MasterPact NW40H1 provides 65kA ultimate short-circuit breaking capacity (Icu) at 440V AC. Its service breaking capacity (Ics) is also 65kA, while its short-time withstand current (Icw) is rated at 65kA for 1 second and 3 seconds. The breaker is Category B and suitable for isolation according to IEC 60947-2.

The breaker has a 690V AC rated operational voltage, 1000V insulation voltage and 12kV impulse withstand voltage. The fixed construction is intended for permanent installation in a switchboard, while the supplied bare frame does not include a MicroLogic control/trip unit.

For protection and metering, the appropriate Schneider Electric MicroLogic control unit must be selected separately. For a 4-pole configuration, the final protection arrangement and required accessories should be selected according to the electrical system and single-line diagram.

Specification Details
Manufacturer Schneider Electric
Product Range MasterPact NW
Circuit Breaker Name MasterPact NW40H1
Reference / Catalogue Number 48097
Product Type Air Circuit Breaker / Basic Frame
Application Power Distribution Protection
Rated Current (In) 4000A at 40°C
Number of Poles 4P / 4 Pole
Neutral Position Left
Mounting Mode Fixed
Control Unit Without Control Unit / Trip Unit
Performance Type H1 – 65kA at 440V AC
Rated Operational Voltage (Ue) 690V AC, 50/60Hz
Rated Insulation Voltage (Ui) 1000V AC, 50/60Hz
Rated Impulse Withstand Voltage (Uimp) 12kV
Rated Ultimate Breaking Capacity (Icu) 65kA at 220/415V, 440V, 525V and 690V AC
Rated Service Breaking Capacity (Ics) 65kA at 220/415V, 440V, 525V and 690V AC
Short-Time Withstand Current (Icw) 65kA for 1s / 65kA for 3s
Short-Circuit Making Capacity (Icm) 143kA at 220/415V, 440V, 525V and 690V AC
Selectivity Category Category B
Suitability for Isolation Yes, conforming to IEC 60947-2
Network Type AC
Rated Frequency 50/60Hz
Control Type Push-button
Sensor Rating 2000A / 4000A
Circuit Breaker CT Rating 4000A
Power Dissipation 650W
Maximum Breaking Time 25ms
Maximum Closing Response Time <70ms
Mounting Support Backplate / rails
Connection Rear connection
Connection Pitch 150mm
Mechanical Durability 10,000 cycles without maintenance / 20,000 cycles with maintenance
Electrical Durability Up to 5,000 cycles at 440V AC and 2,500 cycles at 690V AC without maintenance
Dimensions – Height 352mm
Dimensions – Width 537mm
Dimensions – Depth 297mm
Approx. Net Weight 65kg
Ambient Operating Temperature -25°C to +70°C
Storage Temperature -40°C to +85°C
Operating Altitude 0–2,000m without derating; 2,000–5,000m with derating
Protection Rating IP30
Pollution Degree 4
Standard EN/IEC 60947-1, EN/IEC 60947-2
Certification CE, CCC, EAC, ASTA
Mercury Free Yes
Warranty 18 months

Key Features

  • 4000A rated current
  • 4-pole / 4P configuration
  • MasterPact NW40H1 air circuit breaker
  • Fixed-mount construction
  • 65kA H1 breaking capacity at 440V AC
  • 65kA Icu and Ics
  • 65kA short-time withstand current
  • 143kA short-circuit making capacity
  • 690V AC rated operational voltage
  • 1000V insulation voltage
  • 12kV impulse withstand voltage
  • Category B selectivity
  • Suitable for isolation according to IEC 60947-2
  • 2000A / 4000A sensor rating
  • Rear connection
  • Without MicroLogic trip/control unit
  • Suitable for high-current LV power distribution
  • Designed for main incomer, bus-tie and heavy feeder applications

Applications

The Schneider Electric MasterPact NW40H1 4000A ACB is suitable for:

  • Main LV incomer protection
  • Bus coupler / bus-tie applications
  • High-capacity LV switchboards
  • Industrial power distribution
  • Commercial building power systems
  • Data-centre electrical distribution
  • Infrastructure switchboards
  • Heavy industrial facilities
  • Generator distribution systems
  • High-current feeder protection
  • Electrical distribution panels
  • Retrofit and expansion of existing MasterPact NW installations

For applications where the prospective fault current exceeds 65kA, Schneider’s MasterPact NW40H2 is the higher-breaking-capacity version of the 4000A frame.